| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/30/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/30/2010 | CPIERCE1 | HC | REVIEW | Needs Review | |
| 09/30/2010 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 09/30/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/30/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 09/30/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide energy code compliance calculations using the correct climate zone (Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Comment not resolved; schedule of diffusers has been changed to eliminate all diffusers except "D". Coordinate the schedule of diffusers and registers (M601) with the duct layout on sheet M101. Reference: Section 106.3.1, IMC 2006. |