Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01771
Parcel: 13612001N

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM01771
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2010 MARTIN BROWN FIRE REVIEW Approved
07/06/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Replot sheets P201 and P502 so that details A1/P201, A11/P201, and A1/P502 are legible. Reference: Section 103.2.3, UPC 2006.
2. Provide a vacuum relief for the storage-type water heater (located above fixture outlets). Reference: Section 608.7, UPC 2006.
3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
4. Clarify how the air breaks shown for the cubed ice and the crushed ice conform to the requirements of Section 801.2.3, UPC 2006.
07/06/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations using the correct climate zone (Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Clarify the ductwork shown for the three return air grilles located at the north end of the store (M101); the ducts do not appear to be even close to connecting to them. Reference: Section 106.3.1, IMC 2006.
3. Coordinate the schedule of diffusers and registers (M601) with the duct layout on sheet M101. Reference: Section 106.3.1, IMC 2006.
07/06/2010 ROBERT SHERRY WATER REVIEW Approved
07/07/2010 LAITH ALSHAMI ENGINEERING REVIEW Denied Building plans will be reviewed and approved after the development plan has been approved.
07/09/2010 TERRY STEVENS ZONING REVIEW Denied 07/09/2010

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
07/09/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/13/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide a written deferred submittal summary list in letter for to Mr. LeeRay Hanly for additional fee accessment.
2. Please complete your occupancy load calculations on Sheet N101.
3. On Sheet A211, generic accessibility details are not acceptable. Please provide all accessibility code requirements on the actual floor plan and elevations.
4. Delete all reference to "ADA". Change reference to accessibility code requirements to the 2006 IBC, Chapter 11 and ICC (ANSI 117.1 2003 Edition). Change all notes and design details ot meet these standards.
SHEET N102
5. Delete all reference to "ADA". Change reference to accessibility code requirements to the 2006 IBC, Chapter 11 and ICC (ANSI 117.1 2003 Edition). Change all notes and design details to meet these standards.

STRUCTURAL REVIEW COMMENTS
T10CM01771
QUIK TRIP

6. SHEET S101; PLAN: A SECTION IS CUT AT A CONTROL JOINT TO THE LEFT OF GRID LINE 1 AND IS DENOTED AS F13/S1.1. THERE IS NO SHEET S1.1. CLARIFY.
7. SHEET S130 (PLAN); SHEET S510 (SECTION H8): SECTION H8 INDICATES A MASONRY WALL SUPPORTING THE CANTILEVERED ROOF JOIST, WHILE THE PLAN INDICATES A STEEL BEAM. CLARIFY.
8. SHEET S130; PLAN: A SECTION IS CUT AT RTU-2 AND IS DENOTED AS A13/S4.1. THERE IS NO SHEET S4.1. CLARIFY.
9. SHEET S502: SECTIONS P1/P1A, P12/P12A, AND P16: THE SECTIONS DO NOT INDICATE FINISH GRADE. PROVIDE THAT TO ENSURE THE GEOTECHNICAL EVALUATION REQUIREMENTS ARE MET (MINIMUM FOUNDATION DEPTH OF 1'-6" BELOW FINISH GRADE).
10. SHEET S502; SECTION E12: WHAT DOES THE 2'-0" DIMENSION INDICATE? CLARIFY.
11. SHEET S510; SECTION O8: THIS SECTION SHOULD BE CUT ON SHEET S130 IN PLACE OF SECTION H8. VERIFY.
12. SHEET S510; SECTION O12: THE SECTION CUT DENOTED AS O8/S510 SHOULD BE H8/S510. VERIFY.
13. SHEET S520; SECTION P12: THE SECTION CUT DENOTED AS A16/S520 SHOULD BE P16/S520. VERIFY.
14. SHEET S520; SECTION E4: A DIMENSION LINE REFERENCES A-16-A6.1. REVISE.
15. SHEET S601; FOUNDATION NOTE 1: THIS NOTE SHOULD BE CHANGED TO INDICATE THE GEOTECHNICAL EVALUATION THAT WAS USED ON THIS JOB.
16. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

END OF REVIEW
07/13/2010 RONALD BROWN HC REVIEW Denied Reference Building Comments
07/14/2010 SREEVES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2010 SUE REEVES OUT TO CUSTOMER Completed
07/14/2010 SUE REEVES REJECT SHELF Completed