Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01765
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/29/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
07/02/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006. 2. Show the location of the reduced pressure backflow assembly on the drawings and indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code. |
07/06/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space and the shared plumbing systems. Reference: Sections 106.1 and 106.3, IBC 2006. 2. Provide cleanouts sized per Section 707.11, UPC 2006. |
07/06/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006. |
07/13/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; PROJECT DATA: NOTE FOR THE MINIMUM NUMBER OF EXITS REQUIRED SHOULD REFERENCE IBC SECTIONS 1018 AND 1019. VERIFY. 2. SHEET A1.0; PROJECT DATA: NOTE FOR THE MAXIMUM EXIT ACCESS TRAVEL DISTANCE SHOULD REFERENCE IBC TABLE 1016.1. VERIFY. 3. SHEET A1.0; PROJECT DATA: NOTE FOR THE CORRIDOR FIRE RESISTANCE RATING SHOULD REFERENCE IBC TABLE 1017.1. VERIFY. 4. SHEET A1.0; PROJECT DATA: NOTE FOR THE MAXIMUM LENGTH OF DEAD END CORRIDORS SHOULD REFERENCE IBC SECTION 1017.3. VERIFY. 5. SHEET A1.0; PROJECT DATA: NOTE FOR THE SEISMIC DESIGN REQUIREMENTS SHOULD REFERENCE IBC SECTION 1613. VERIFY. 6. SHEET A1.0; PROJECT DATA: NOTE FOR THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES SHOULD LIST THE NUMBER OF OCCUPANTS AS 40. VERIFY. 7. SHEET A2.1; PARTITION 1: PROVIDE A DETAIL INDICATING THE TOP OF THE WALL BRACING TO MEET IBC SECTION 1607.13 REQUIREMENTS. INCLUDE THE BRACE SIZE AND SPACING, CONNECTION TO THE EXISTING STRUCTURE, AND CONNECTION TO THE TOP OF THE PARTITION WALL. 8. SHEET A2.1; DOOR SCHEDULE: THE TWO EXIT DOORS ARE NOT INCLUDED IN THE SCHEDULE. ARE THESE EXISTING DOORS? CLARIFY. 9. SHEET A2.1 (PLAN); SHEET G-1: PROVIDE DETAILS AND DIMENSIONS FOR THE ROLL-IN-TYPE SHOWER PER ICC/ANSI CHAPTER 6. 10. GENERAL: PROVIDE THE SHELL DRAWINGS FOR REVIEW COORDINATION. 11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
07/14/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
07/20/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
07/22/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/28/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
07/28/2010 | SUE REEVES | REJECT SHELF | Completed |