Permit Number: T10CM01765
Parcel: 110162860

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01765
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2010 DAVE MANN FIRE REVIEW Approved
07/02/2010 ROBERT SHERRY WATER REVIEW Denied 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
2. Show the location of the reduced pressure backflow assembly on the drawings and indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code.
07/06/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space and the shared plumbing systems. Reference: Sections 106.1 and 106.3, IBC 2006.
2. Provide cleanouts sized per Section 707.11, UPC 2006.
07/06/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006.
07/13/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; PROJECT DATA: NOTE FOR THE MINIMUM NUMBER OF EXITS REQUIRED SHOULD REFERENCE IBC SECTIONS 1018 AND 1019. VERIFY.
2. SHEET A1.0; PROJECT DATA: NOTE FOR THE MAXIMUM EXIT ACCESS TRAVEL DISTANCE SHOULD REFERENCE IBC TABLE 1016.1. VERIFY.
3. SHEET A1.0; PROJECT DATA: NOTE FOR THE CORRIDOR FIRE RESISTANCE RATING SHOULD REFERENCE IBC TABLE 1017.1. VERIFY.
4. SHEET A1.0; PROJECT DATA: NOTE FOR THE MAXIMUM LENGTH OF DEAD END CORRIDORS SHOULD REFERENCE IBC SECTION 1017.3. VERIFY.
5. SHEET A1.0; PROJECT DATA: NOTE FOR THE SEISMIC DESIGN REQUIREMENTS SHOULD REFERENCE IBC SECTION 1613. VERIFY.
6. SHEET A1.0; PROJECT DATA: NOTE FOR THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES SHOULD LIST THE NUMBER OF OCCUPANTS AS 40. VERIFY.
7. SHEET A2.1; PARTITION 1: PROVIDE A DETAIL INDICATING THE TOP OF THE WALL BRACING TO MEET IBC SECTION 1607.13 REQUIREMENTS. INCLUDE THE BRACE SIZE AND SPACING, CONNECTION TO THE EXISTING STRUCTURE, AND CONNECTION TO THE TOP OF THE PARTITION WALL.
8. SHEET A2.1; DOOR SCHEDULE: THE TWO EXIT DOORS ARE NOT INCLUDED IN THE SCHEDULE. ARE THESE EXISTING DOORS? CLARIFY.
9. SHEET A2.1 (PLAN); SHEET G-1: PROVIDE DETAILS AND DIMENSIONS FOR THE ROLL-IN-TYPE SHOWER PER ICC/ANSI CHAPTER 6.
10. GENERAL: PROVIDE THE SHELL DRAWINGS FOR REVIEW COORDINATION.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/14/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
07/20/2010 GERRY KOZIOL WWM REVIEW Approved
07/22/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2010 CPIERCE1 OUT TO CUSTOMER Completed
07/28/2010 SUE REEVES REJECT SHELF Completed