Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01737
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2011 | CPIERCE1 | ZONE H/C | REVIEW | Needs Review | |
| 12/09/2010 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approv-Cond | Laith Alshami, Engineering and Floodplain Review, 12/09/2010, Approved conditionally subject to keeing the building foundation at the building corner touching the building setback, outside the building setback area. |
| 12/09/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED REVIEW/APPROVAL FOR CAPCITY EVALUATION AND /OR POINT/METHOD OF CONNECTION- PCRWRD DEV LIAIDON UNIT- 3RD FLOOR PWB- 740-6534 CITY OF TUCSON APPROVED DEV PLAN D09-0036 POINT OF CONNECTION ON D. P. |
| 12/09/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/13/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Sheet P3 indicates that a 1-1/2" water meter will be serving the new building and references the civil drawings. Sheet P1, however, still calls for a 1" water meter and also references the civil drawings. The closest thing to a civil drawing appears to be sheet A1, which also shows a 1" water service for the building. Sheet P1 indicates the location of the backflow preventer but does not locate the water meter. Coordinate the drawings to clearly show what is being installed and the locations for the water meter and the backflow preventer. Reference: Section 103.2.3, UPC 2006. |
| 12/14/2010 | TERRY STEVENS | ZONING | REVIEW | Approved |