Permit Number: T10CM01733
Parcel: 129041750

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM01733
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2010 DAVE MANN FIRE REVIEW Approved
08/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.1; SPECIAL STRUCTURAL INSPECTIONS (NOTE 42): REPLACE REFERENCE TO 'TOWN OF MARANA' WITH 'CITY OF TUCSON'.
2. SHEET A1.1; GEOTECHNICAL (NOTE 12): IF A GEOTECHNICAL REPORT IS REFERENCED, PROVIDE FOR REVIEW.
3. SHEET A3.0; KEYNOTES: COULD NOT LOCATE NOTES 7, 12, 13, OR 15 ON THE PLANS OR ELEVATIONS. VERIFY.
4. SHEET A3.0; DIMENSIONED PLAN AND FOUNDATION PLAN: THERE ARE SEVERAL DIMENSION LINES ON BOTH PLANS THAT HAVE LETTERING LESS THAN 3/32" IN HEIGHT AS REQUIRED BY CITY OF TUCSON STANDARDS. REVISE.
5. SHEET A3.1 (DETAIL 3); STRUCTURAL CALCULATIONS (PAGE 8): THE CALCULATIONS INDICATE AN EXISTING W10X21 STEEL BEAM AT THIS DETAIL WHILE THE DRAWING INDICATES A W8X17. CLARIFY.
6. SHEET A3.2 (DETAIL 13); SHEET A3.1 (DETAIL 3): DETAIL 3 (PLAN) INDICATES THE HSS4X4X.188 IS TO BE BOLTED TO THE 4X4 WOOD POSTS. CLARIFY HOW THIS IS TO BE ACCOMPLISHED (PROVIDE A DETAIL). THE CALCULATION INDICATES A SEAT CONNECTION (PAGE 8).
7. SHEET A3.2 (DETAIL 13); SHEET A3.1 (DETAIL 3): DETAIL 3 (PLAN) INDICATES A 4X4 STRUT. SHOW THIS MEMBER ON THE SECTION.
8. GENERAL; THE LOOSE STRUCTURAL CALCULATIONS (NOT BOUND IN SET): WHAT ARE THESE FOUR CALCULATIONS IN REFERENCE TO? THERE ARE NO
5 1/8"X 10 1/2" GLULAMS, 5 1/8"X 13 1/2" GLULAMS, OR 2X8'S INDICATED ON THE DRAWINGS. VERIFY.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
08/31/2010 SUE REEVES REJECT SHELF Completed