Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM01691
Parcel: 12106001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01691
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved As per Eric's previous review
07/06/2010 ROBERT SHERRY WATER REVIEW Approved
07/06/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/06/2010 RONALD BROWN ZONING HC REVIEW Approved As per Eric's previous review
07/06/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/11/2010 STEVE SHIELDS ZONING REVIEW Approved