Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01691
Parcel: 12106001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01691
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1; PROJECT CODE REVIEW: REVIEW THE OCCUPANT LOAD. 100 SF/OCCUPANT IS USED FOR BUSINESS OCCUPANCIES, NOT MERCANTILE.
2. SHEET A1.0; FLOOR PLAN (ENLARGED RESTROOM PLAN): THE ENLARGED RESTROOM PLAN DOES NOT MATCH THE FLOOR PLAN (LOCATION OF DOORS). CLARIFY.
3. SHEET A1.0; ENLARGED RESTROOM PLAN: VERIFY THE MANEUVERING CLEARANCE AT THE RESTROOM DOORS MEETS THE REQUIREMENT OF ANSI FIGURE 404.2.3.1(b).
06/22/2010 JASON GREEN ENGINEERING REVIEW Approved
06/22/2010 ERIC NEWCOMB ADA REVIEW Passed
06/22/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/22/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
06/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Does the new restroom have an exhaust fan capable of exhausting at least 75 CFM?
06/23/2010 MARTIN BROWN FIRE REVIEW Approved
06/23/2010 ROBERT SHERRY WATER REVIEW Denied Identify the size of the existing backflow protection for the water service, the size of the water meter serving this suite, and the total demand of the water meter.
06/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a complete plumbing plan, including a waste and vent riser, materials of construction, and specifications for the new fixtures.
2. Show how the water for the new lavatory is to be limited to a maximum temperature of 110 degrees Fahrenheit.
07/06/2010 GERRY KOZIOL WWM REVIEW Approved
07/06/2010 GBONILL1 ZONING REVIEW Needs Review