Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T10CM01690
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/16/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/16/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
| 08/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Automatic clothes washers (see room 122) have quick-closing valves. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006 |
| 08/31/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approv-Cond | |
| 09/02/2010 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/02/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |