Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01690
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2010 | MARTIN BROWN | FIRE | REVIEW | Denied | Per 2006 IFC, Section 3006, medical gases shall be stored in areas dedicated to storage of gases without storage or other uses. Please indicate types and quantities of Med Gases stored in room 122. Refence IFC for maximum allowable quantities. Please include conversions, if necessary. |
| 06/28/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Toilets: a. The lav counter encroaches on clear space required for water closet at toilet 102. b. Generic details are not acceptable for accessible requirements. Please provide large scale toilet plans and large scale toilet elevations for all toilet rooms. Please provide all critical required accessible design elements as per ICC (ANSI 117.1). 2. Please provide drinking fountains as required by 2006 IBC, ICC (ANSI 117.1), Section 602. 3. Please provide structural details and calculations for the following: a. Water heater b. All roof top mounted HVAC units 4. The gas storage looks ok depending on quantities of gas being stored. Reference Fire comments. END OF REVIEW |
| 06/28/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | Reference Building comments |
| 06/29/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The 1" pipe size serving the flush valve for the water closet in restroom 102 (on the domestic water piping schematic) will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 2. Confirm the water calculations; the calculations indicate that the water meter has moved closer to the building since the shell was constructed. 3. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006. 4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006. |
| 06/29/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/29/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/16/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | need ww credit evaluation- 5th floor-740-6544 |
| 07/19/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM01690, 6452 E Carondelet, #150 Sheet E2.0, lighting plan, circuit B-13 feeds what type of lights, also circuir B-1 is not listed on the lighting plan for the lights it feeds. Ray T Majuta,PDSD,City of Tucson, Elect Pln CK 7/22/10 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/23/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 07/23/2010 | SUE REEVES | REJECT SHELF | Completed |