Permit Number: T10CM01690
Parcel: 13317062G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01690
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2010 MARTIN BROWN FIRE REVIEW Denied Per 2006 IFC, Section 3006, medical gases shall be stored in areas dedicated to storage of gases without storage or other uses.
Please indicate types and quantities of Med Gases stored in room 122. Refence IFC for maximum allowable quantities. Please include conversions, if necessary.
06/28/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Toilets:
a. The lav counter encroaches on clear space required for water closet at toilet 102.
b. Generic details are not acceptable for accessible requirements. Please provide large scale toilet plans and large scale toilet elevations for all toilet rooms. Please provide all critical required accessible design elements as per ICC (ANSI 117.1).
2. Please provide drinking fountains as required by 2006 IBC, ICC (ANSI 117.1), Section 602.
3. Please provide structural details and calculations for the following:
a. Water heater
b. All roof top mounted HVAC units
4. The gas storage looks ok depending on quantities of gas being stored. Reference Fire comments.
END OF REVIEW
06/28/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Building comments
06/29/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The 1" pipe size serving the flush valve for the water closet in restroom 102 (on the domestic water piping schematic) will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
2. Confirm the water calculations; the calculations indicate that the water meter has moved closer to the building since the shell was constructed.
3. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006.
4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
06/29/2010 ROBERT SHERRY WATER REVIEW Approved
06/29/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/16/2010 GERRY KOZIOL WWM REVIEW Denied need ww credit evaluation- 5th floor-740-6544
07/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM01690, 6452 E Carondelet, #150


Sheet E2.0, lighting plan, circuit B-13 feeds what type of lights, also circuir B-1 is not listed on the lighting plan for the lights it feeds.

Ray T Majuta,PDSD,City of Tucson,
Elect Pln CK
7/22/10
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2010 DELMA ROBEY OUT TO CUSTOMER Completed
07/23/2010 SUE REEVES REJECT SHELF Completed