Permit Number - T10CM01664
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2010 DAVE MANN FIRE REVIEW Approved
06/25/2010 BIANCA RAMIREZ ENGINEERING REVIEW Denied Site Plan Denied -

1. Please see section 2-02.2.1 and revise site plan plan to meet minimum submittal requirements for site plan.

2. Handicap sign should read $532 FINE

3. Floodplain Use Permit Required

4. All zoning and landscaping comments must be addressed prior to engineering approval.

5. Additional comments will be forthcoming.

Bianca Ramirez
06/28/2010 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Landscaping requirements apply to expansion of existing development as follows:

2. On sites where the gross floor area of the existing building(s) is more than ten thousand (10,000) square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows:

3. If the expansion is less than 25%, the requirements of this Division apply only to the proposed expansion. Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B. Provide a plan that shows how the site meets minimum landscape requirements indicated on approved landscape plan dated 12-20-1999.

4. Any plant material in areas of required landscaping that does not survive or has been removed will be replaced with an equivalent size and species DS 2-06.6.1

5. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

6. Additional comments may apply
06/29/2010 ANDREW CONNOR NPPO REVIEW Approved Exception
06/29/2010 RONALD BROWN ZONING HC REVIEW Denied 1. At detail 4/C1.0, please provide a "Van Accessibele" sign and identify which space is the "Van Accessible" space on detail 2/C1.0.
2. Detectable Warning strip not required at access to parking aisle.
3. Provide an exterior accessible route from the accessible parking to the Customer Servise drive and offices.
4. Show all grades on accessible route to comple with 2006 IBC, ICC (ANSI 117.1), Section 403.3.
5. The Site Plan needs to be at a bigger scale to show accessible compliance in more detail.
6. Please provide an accessible parking space at the Customer Service Drive and Offices.
END OF REVIEW
06/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location of the gas meter
d. the location and size of the public sanitary sewer
e. the location of the building connection to the public sewer
f. the location, invert, and rim elevation of all manholes and cleanouts
g. the first floor elevation for the building
Reference: City of Tucson Development Standard No. 2-01.1.0 2 3.8 D and Section 103.2.3, UPC 2006.