Permit Number: T10CM01647
Parcel: 11451216G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01647
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2010 STEVE SHIELDS ZONING REVIEW Approved
06/17/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project T10CM01647, 9095 E Tanque Verde

Electrical denied: The load calculations in the panel schedule are inconsistant, some circuirts show no loads, others are insufficiently loaded. Provide an up to date load calculation showing all true loads in the panel schedulke,include all lighting and power usage.

R T Majuta.C of T, PDSD,
Elect Pln CK,
6/17/10
Ray.Majuta@tucsonaz.gov
06/17/2010 ROBERT SHERRY WATER REVIEW Approved
06/17/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/17/2010 LOREN MAKUS ENGINEERING REVIEW Approved
06/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/17/2010 MARTIN BROWN FIRE REVIEW Approved
06/17/2010 ERIC NEWCOMB ADA REVIEW Passed
06/17/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/17/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
06/24/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2010 DELMA ROBEY OUT TO CUSTOMER Completed