Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01627
Parcel: 133541120

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM01627
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM01627
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Provide two sets of construction drawing for processing, R106.1.1.
" Provide manufacturer specification sheets for collector panels, inverter and mounting hardware.
DIAGRAMS / CALCULATIONS
1. Show a DC grounding electrode conductor size equal to the DC supply conductors and not smaller than #8 (copper), NEC 250.166 (B).
NOTES / SPECIFICATIONS
1. Provide the exact wording and location for the DC Power Source "Imp, Vmp, Vmax, Isc" marking required by NEC 690.53.
2. Provide the location for the "backfed" circuit breaker in compliance with NEC 690.64 (B) (5).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2010 GERARDO BONILLA REJECT SHELF Completed