Permit Number: T10CM01603
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01603
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/15/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM01603
4004 S Park Av #1

Electrical denied for following:
1. Circuits PN 36,38,40 shown on power plan twice, and not shown on Panel Schedule.

Ray T Majuta, Elect Pln Ck,
PDSD, City of Tuc
6/15/10
520.837.7988
06/15/2010 ROBERT SHERRY WATER REVIEW Approved
06/15/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/15/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
06/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/15/2010 RONALD BROWN ADA REVIEW Passed Not required
06/15/2010 RONALD BROWN ZONING HC REVIEW Passed Not Required
06/16/2010 JASON GREEN ENGINEERING REVIEW Approved June 16, 2010
FLOODPLAIN USE PERMIT NO.: T10OT01310
ADDRESS: 4004 S Park Ave #1 Tucson, Arizona 85714
PROPERTY OWNER: City of Tucson
4004 S Park Ave #1 Tucson, Arizona 85714

The applicant is authorized to use a portion of the City of Tucson Flood Hazard Area per the Desert Shadows Wash delineation, specifically described as:

A portion of Parcel 132-16-600A, IRREG PORTIONS OF W2 NW4 56.55 AC SEC 31-14-14
For the purpose of a tenant improvement to an existing non-conforming structure.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

This floodplain use permit is issued with the following 13 conditions:
1) All improvements proposed under this permit will be cumulative in percentage, to include this project.
2) The proposed improvements shall not impose conditions that would increase the flood damage potential to the combined proposed and existing building, by 50 percent or greater of the existing structure's value.
3) The building valuation was provided showing that the improvements are less than 50 % (estimate was 0.2%) of the assessed value as shown on FUP T09OT01584 ($471,155). No person shall repair or alter property in a piecemeal manner so as to avoid the provisions of Section 26-4.1.a.3, Chapter 26-Tucson Code. The estimate will be recorded and if piecemeal permits for this construction are applied for the cost estimate will be added to it.
4) All work shall conform to the approved Details and General site plan sheets which are made part of this permit.
5) This project is located in a City of Tucson Flood Hazard Area per the City of Tucson Mapguide Floodplain delineation of Desert Shadows Wash.
6) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
7) This Floodplain Use Permit is issued concurrently with the improvement plans/permit. Copies of these documents shall be kept in a readily accessible location on site at all times.
8) Any future permanent, freestanding walls or other structures shall have separate floodplain use permit applications submitted to this office for review and approval.
9) An application/processing fee of $50.00 (submittal fee) must accompany each future request for work to be authorized under this floodplain use permit. Engineering study review fees of $150.00 may be imposed based upon the fee schedule in the current floodplain ordinance.
10) The associated improvements are with permit activity number T10CM01603.
11) The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be done to the existing building, and that all additions, improvements or repairs to the building are included in the construction plans and/or documents herewith. No other improvements, repairs, reconstruction, additions or remodeling have been made to the structure that is not indicated in the attached plans and/or documents.
12) Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Division. This permit may be renewed for up to one year at the sole discretion of the City Engineer or designated representatives.
13) This permit is specific to the improvements for 4004 S Park Ave #1 as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Division. This permit may be renewed for up to one year, in the absence of Registered Plant authorization, at the sole discretion of the City Engineer or designated representatives.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Metro Permit
ADDRESS: 3619 E Speedway Bl #101 Tucson, Arizona 85716
PHONE: 520-990-6866
OWNER: City of Tucson
ADDRESS: 4004 S Park Ave #1 Tucson, Arizona 85716
PHONE: 520-791-5111

(EXPIRATION DATE) Month: _06 Day: 16 Year: 2011

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
06/16/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
06/16/2010 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2010 DELMA ROBEY OUT TO CUSTOMER Completed