| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide completed Special Inspections Certificates for review and approval as called for in attached Modi and Company correspondance dated 19 May 2010. 2. Also as per Modi and Company correspondence, the steel joist should be strenghtened according to detail 209 noted on sheet S-504 as required unless the concentrated load is placed within 6" from the joist top cord panel point. Please submit Sheet S-504, for review of Detail S-504. END OF REVIEW |
| 07/07/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM01597, 401 S Prudence Photovoltaic System The Electrical Plans have been denied for the following: 1. Provide the location on plans for all Photovoltaic equipment including inverter, AC disconnects and PV Meter. 2. Provide a location for AC existing service. 3. Point of connection of PV source to AC system per 2005 NEC 690.64 has to be either at supply or load side of disconnecting means. 4. Provide notation on plans to provide markings as required per 690.14 C 2, 17 , 53 , and 56 B. Ray T Majuta,Elect Pln Ck PDSD, City of Tucson, 7/8/10 Ray.Majuta@tucsonaz.gov |