Permit Number: T10CM01591
Parcel: 11515021F

Address:
2301 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01591
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2010 DAVE MANN FIRE REVIEW Approved
06/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
06/14/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
06/14/2010 ROBERT SHERRY WATER REVIEW Approved
06/14/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide point of use drinking fountain
2. New interior partitions need laterial bracing to above structure detailed and/or noted.
3. Lettering font standard is 3/32" minimum, upper and lower case. Please revise all drawings that don not meet this standard and resubmit.
END OF REVIEW
06/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006.
06/14/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/14/2010 RONALD BROWN ADA REVIEW Passed
06/14/2010 RONALD BROWN ZONING HC REVIEW Approved
06/17/2010 GBONILL1 WWM REVIEW Needs Review
06/17/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
06/17/2010 PAUL MACHADO ENGINEERING REVIEW Approved