Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01591
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
06/14/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
06/14/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/14/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/14/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide point of use drinking fountain 2. New interior partitions need laterial bracing to above structure detailed and/or noted. 3. Lettering font standard is 3/32" minimum, upper and lower case. Please revise all drawings that don not meet this standard and resubmit. END OF REVIEW |
06/14/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. 2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006. |
06/14/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/14/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
06/14/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
06/17/2010 | GBONILL1 | WWM | REVIEW | Needs Review | |
06/17/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/17/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |