Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01585
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/03/2010 | Michael Wyneken | ZONING-CITY HALL | REVIEW | Approved | |
08/05/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/05/2010 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Approved | |
08/05/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/05/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 2; SHEET 13; FABRIC SUPPORT PLAN: YOUR RESPONSE INDICATED THE STRUCTURAL CALCULATIONS FOR THE SHADE SCREEN SUPPORTS AND ANCHORS WERE INCLUDED. THEY WERE NOT LOCATED. 2. SHEET 01; DRAWING INDEX: TWO SHEET NUMBERS ARE DESIGNATED AS 'A' (FOR THE POLE AND FOUNDATION STRUCTURE' AND 'STRUCTURAL DETAILS'). REVISE. 3. GENERAL: STRUCTURAL WELDING MUST BE ADDED TO THE SPECIAL INSPECTION CERTIFICATE (SEE SHEET PF1/B, DETAIL 2). 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
08/12/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
08/16/2010 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |