Permit Number: T10CM01585
Parcel: 99999999C

Address:
4595 E GRANT RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM01585
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2010 MARTIN BROWN FIRE REVIEW Approved
06/17/2010 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
06/18/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T10CM01585
New MonoPalm
4415 E. Grant.

TRANSMITTAL DATE: June 18, 2010

1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Provide a copy of the site plan that is referenced under the "PARKING CALCULAITONS **".

3. Provide a setback dimension from the proposed 8' high block wall enclosure to the east property line. Per LUC Section 3.2.6.4, perimeter yard indicator "CC" the required perimeter yard to the east property line is the height of the structure or 8'-0".

4. Per D.S. 3-05.2.1.3 When the side(s) of a parking space abuts any vertical barrier over six (6)
inches in height, other than a vertical support for a carport, the required width for the space is ten (10) feet to provide extra width to allow passengers to enter and exit the vehicle on the side where the barrier exists. That said provide a width dimension for the vehicle parking space directly north of the equipment enclosure so that the requirements of D.S. 3-05.2.1.3 can be verified.

4. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the above comments. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\celltower\t10cm01585.doc
06/30/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 06; DETAIL D04: PROVIDE STRUCTURAL CALCULATIONS FOR THE CMU WALL AND FOOTING.
2. SHEET 13; FABRIC SUPPORT PLAN: PROVIDE STRUCTURAL CALCULATIONS FOR THE SHADE SCREEN SUPPORTS AND ANCHORS.
3. GENERAL: SPECIAL INSPECTION CERTIFICATE MUST LIST THE NAMES OF EACH INSPECTOR FOR THE VARIOUS CATEGORIES.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/06/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved
07/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2010 CPIERCE1 OUT TO CUSTOMER Completed
07/28/2010 SUE REEVES REJECT SHELF Completed