Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM01584
Parcel: 13623009B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01584
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2012 MICHAEL ST. PAUL ZONING REVIEW Needs Review
11/19/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Comment not addressed. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
11/19/2012 ROBERT SHERRY WATER REVIEW Approved
11/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The minimum static pressure at the water meter is in excess of 80 PSIG; provide a pressure reducing valve. Reference: Sections 608.2 and 610.7 (5), UPC 2006. [Original comment: Clarify the how the submitted water pressure calculations are coordinated with the note on the plumbing plan (P1.0) that calls for a "PRV set at 70 PSI".]
12/10/2012 CAGUILA1 WWM REVIEW Needs Review
12/10/2012 CAGUILA1 FIRE REVIEW Needs Review
12/10/2012 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review