Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01584
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Needs Review | |
| 11/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Comment not addressed. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. |
| 11/19/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The minimum static pressure at the water meter is in excess of 80 PSIG; provide a pressure reducing valve. Reference: Sections 608.2 and 610.7 (5), UPC 2006. [Original comment: Clarify the how the submitted water pressure calculations are coordinated with the note on the plumbing plan (P1.0) that calls for a "PRV set at 70 PSI".] |
| 12/10/2012 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 12/10/2012 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 12/10/2012 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |