Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01567
Parcel: 125150860

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM01567
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
10/25/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS: NO CALCULATIONS FOR THE 2X10 AND 3X10 LEDGERS AND ANCHORS WERE LOCATED. PROVIDE.
2. SHEET S2.0; FOUNDATION PLAN NOTES: NOTE 9 WAS NOT FOUND ON THE PLAN. VERIFY.
3. SHEET S2.0; FOUNDATION PLAN: PROVIDE A DETAIL AT THE NEW COLUMN FOOTING F1 AT THE LAUNDRY ROOM ADDITION. INDICATE HOW THE NEW FOOTING IS CONSTRUCTED AROUND THE EXISTING FOUNDATION.
4. SHEET S2.0; ROOF FRAMING PLAN: PROVIDE A NOTE AT THE NEW LAUNDRY ROOM ADDITION STEEL LINTEL, INDICATING TEMPORARY SHORING OF THE EXISTING WALL.
5. SHEET S3.0; DETAILS 1 AND 2: PROVIDE A NOTE REFERRING THE CMU FOUNDATION WALL TO THE GENERAL NOTES.
6. SHEET S4.0; DETAIL 9: CALL OUT THE NEW PLYWOOD AND NAILING ON THE BOTTOM OF THE EXISTING CEILING FRAMING.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2010 CPIERCE1 OUT TO CUSTOMER Completed
11/04/2010 SUE REEVES REJECT SHELF Completed