Permit Number: T10CM01566
Parcel: 11307150A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM01566
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical denied, the fault current figures are to be provided on the original plan signed and sealed by EE. provide the fault current at the new 400 amp main in the switchgear, and the fault current at the 400 amp disconnect for the PV system.


Ray T Majuta
PDSD, City of Tuc.
Elect Pln Ck,
8/4/10
520/837/4988

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2010 CPIERCE1 OUT TO CUSTOMER Completed