Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T10CM01566
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10cm01566 1. The new 400 a PV Disconnect becomes a Main Disconnect and must be grouped with other mains at the 800 amp service inside the Electrical Room, unless the switchgear has six already, then it would not be allowed. 2. Provide a fault currernt analysis for new main from service to let-thur to system. Ray T Majuta Elect Pln CK 7/29/10 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/30/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |