Permit Number: T10CM01566
Parcel: 11307150A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM01566
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10cm01566

1. The new 400 a PV Disconnect becomes a Main Disconnect and must be grouped with other mains at the 800 amp service inside the Electrical Room, unless the switchgear has six already, then it would not be allowed.
2. Provide a fault currernt analysis for new main from service to let-thur to system.

Ray T Majuta
Elect Pln CK
7/29/10

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2010 CPIERCE1 OUT TO CUSTOMER Completed