Review Details: RESUBMITTAL
Permit Number - T10CM01566
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM01566,1510 E FT LOWELL 89,635 w Photovoltaic System, 293 modules Electrical denied for following: 1. New (5) lights to be installed under new parking structure, provide cut sheet with information of type,voltage,amperage,lumens,and FCO or Shielde type. 2. Provide a discription of type of connection , to how many conductors will connection be made too, is there sufficient room, etc. 3. Provide a load calculation on the total existing load plus load added by Inverters for total load to be put on primary conductors. Ray T Majuta PDSD, City of Tucson, Elect Pln Ck 7/22/10 Ray.Majuta@tucsonaz.gov |