Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01566
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. STRUCTURAL CALCULATIONS (BY B. MIDDLESWART); PAGE D1: THE LIVE LOAD IS LISTED AS 'N/A'. VERIFY THAT THE ROOF LIVE LOADS LISTED IN THE IBC TABLE 1607.1 ARE NOT APPLICABLE TO THE CANOPY DESIGN. REVISE CALCULATIONS AND DRAWINGS AS REQUIRED. 2. GENERAL (CANOPY): PROVIDE FULL SIZE DRAWINGS OF THE CANOPY, INCLUDING FOUNDATION AND FRAMING PLANS, GENERAL STRUCTURAL NOTES, AND DETAILS/SECTIONS AS REQUIRED. 3. GENERAL: THE LETTERING HEIGHT FOR ALL SHEETS MUST BE A MINIMUM OF 3/32" PER CITY OF TUCSON STANDARDS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/19/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 07/19/2010 | SUE REEVES | REJECT SHELF | Completed |