Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T10CM01561
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: The site plans Sheet 11 indicate the building has fire sprinklers. the fire hydrant is just over 300 feet from the most remote point on the building. The building plans do not show a sprinkler system. Please clarify. A small change in the hydrant location may be required. |
| 06/16/2010 | JASON GREEN | ENGINEERING | REVIEW | Denied | Provide a copy of the stamped aprroved development plan S09-081 for building plan and canopy stamp approval. The plans may be brought through as a counter walk through once the development plan package has been finalized through CDRC. |
| 06/17/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET AB2; STRUCTURAL CALCULATIONS (BASE PLATE DESIGN): THE BASE PLATE INDICATED ON THE DRAWINGS (1 1/2"X22"X1'10") DOES NOT MATCH THE CALCULATIONS STANDARD BASE PLATE DRAWING (1 1/2"X18"X1'-6"). CLARIFY. 2. SHEET E1 (CANOPY FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 11): THE COLUMN CALL-OUT ON THE FRAMING PLAN IS TS10X10X1/4, BUT THE CALCULATIONS LIST A TS10X10X5/16. CLARIFY. 3. STRUCTURAL CALCULATIONS: DID NOT LOCATE THE ANCHOR BOLT DESIGN AT THE COLUMNS. VERIFY. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 06/18/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/18/2010 | ERIC NEWCOMB | HC | REVIEW | Approved | |
| 06/21/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Quick Trip T10CM01560 & T10CM01561 Building Plan (1st Review) TRANSMITTAL DATE: June 21, 2010 1. The building plan has been reviewed by Zoning Review Section and matches what is shown on the approved development package. Once all other PDSD agencies have approved Zoning will approve the building and fuel canopy plans. 2. Zoning is available for an over-the-counter review once all other PDSD agencies have approved the plans. Please call or email to schedule an appointment for the review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t10cm01560.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/27/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 07/27/2010 | SUE REEVES | REJECT SHELF | Completed |