Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01551
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/27/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
08/27/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The 2006 UPC restricts the use of flared joints to non-ferrous tubing in systems where "experience and testing have demonstrated that the joint is suitable for the conditions and where provisions have been made in the design to prevent separation of the joints." Provide justification for the use of flared fittings for this installation. Reference: Section 1209.5.8.3, UPC 2006. |
08/30/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/02/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
09/02/2010 | SUE REEVES | REJECT SHELF | Completed |