Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01551
Parcel: 11706315E

Address:
450 S TOOLE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01551
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2010 JASON GREEN ENGINEERING REVIEW Approved
08/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The 2006 UPC restricts the use of flared joints to non-ferrous tubing in systems where "experience and testing have demonstrated that the joint is suitable for the conditions and where provisions have been made in the design to prevent separation of the joints." Provide justification for the use of flared fittings for this installation. Reference: Section 1209.5.8.3, UPC 2006.
08/30/2010 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/02/2010 SUE REEVES REJECT SHELF Completed