Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01545
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | needs ww credit evaluation- 5th floor- 740-6544 need capasity evaluation by PCRWRD- KURT STEMM 740-6607 |
| 07/09/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the plumbing fixtures and drainage fittings installed correctly and in a manner consistent with the Code and the manufacturer's instructions (e.g. the upstream cleanout for the gravity grease interceptor). Reference: Sections 304.0, 310.4, and 707.6, UPC 2006. 2. Verify that the installation of the gravity grease interceptor complies with the requirements of Section 313.3, UPC 2006. 3. Resize the drainage piping to conform to Table 7-5, UPC 2003, with no more than 8 fixture units on a 2" horizontal waste line. Reference: Section 703.2, UPC 2006 4. Revise the indirect waste piping for the food service equipment to comply with the requirements of Section 803.0 with respect to length. (Note that the indirect waste line from P3 is less than 5-feet in length and does not require a trap.) Reference: Section 803.0, UPC 2006. 5. Resize the proposed grease interceptor per Section 1014.3.6, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/15/2010 | DELMA ROBEY | APPROVAL SHELF | Completed |