Permit Number: T10CM01512
Parcel: 10321342A

Address:
2106 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01512
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the revision to sheet H1 shows a perforated stainless steel wall covering behind the hood. Verify that a non-combustible, nonabsorbent, and cleanable material that will extend at least 18" beyond the hood is being installed. Reference: Section 507.9, IMC 2006.
08/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2010 SUE REEVES OUT TO CUSTOMER Completed