Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01512
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; the revision to sheet H1 shows a perforated stainless steel wall covering behind the hood. Verify that a non-combustible, nonabsorbent, and cleanable material that will extend at least 18" beyond the hood is being installed. Reference: Section 507.9, IMC 2006. |
| 08/23/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/23/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |