Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01512
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2010 | RONALD BROWN | HC | REVIEW | Approved | |
| 07/22/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/03/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; the wall description given in the response letter doesn't match with UL type U408 wall construction. The question is simple: does the wall have non-combustible supports (e.g. steel studs)? Verify the construction of the wall behind the Type I grease hood and show that the clearances required by Section 507.9, IMC 2006 are being maintained. 2. Comment not resolved; the revision to sheet H1 does not specifically address the wall covering behind the hood. Verify that a non-combustible, nonabsorbent, and cleanable material that will extend at least 18" beyond the hood is being installed. Reference: Section 507.9, IMC 2006. |
| 08/03/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved. Section 704.3 requires the wash and rinse sections of the 3-compartment sink to be directly-connected to the sanitary sewer system; Section 801.2.3 requires the sanitizing compartment to be indirectly-connected to the sanitary sewer system. Provide an indirect waste connection only for the sanitizing compartment of the 3-compartment sink. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. |
| 08/10/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/20/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 08/20/2010 | SUE REEVES | REJECT SHELF | Completed |