Permit Number: T10CM01512
Parcel: 10321342A

Address:
2106 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01512
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2010 RONALD BROWN HC REVIEW Approved
07/22/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; the wall description given in the response letter doesn't match with UL type U408 wall construction. The question is simple: does the wall have non-combustible supports (e.g. steel studs)? Verify the construction of the wall behind the Type I grease hood and show that the clearances required by Section 507.9, IMC 2006 are being maintained.
2. Comment not resolved; the revision to sheet H1 does not specifically address the wall covering behind the hood. Verify that a non-combustible, nonabsorbent, and cleanable material that will extend at least 18" beyond the hood is being installed. Reference: Section 507.9, IMC 2006.
08/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Section 704.3 requires the wash and rinse sections of the 3-compartment sink to be directly-connected to the sanitary sewer system; Section 801.2.3 requires the sanitizing compartment to be indirectly-connected to the sanitary sewer system. Provide an indirect waste connection only for the sanitizing compartment of the 3-compartment sink. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
08/10/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
08/20/2010 SUE REEVES REJECT SHELF Completed