Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T10CM01502
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | issued with grease trap need 5th floor credit evaluation needs to show locatpion/method of connection to public sewer- Chad - 3rd floor |
| 06/25/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/25/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/28/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; sheet P1 is illegible. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. |
| 06/29/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
| 06/29/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/08/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 07/08/2010 | SUE REEVES | REJECT SHELF | Completed |