Permit Number: T10CM01502
Parcel: 11205283E

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM01502
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2010 GERRY KOZIOL WWM REVIEW Denied issued with grease trap
need 5th floor credit evaluation
needs to show locatpion/method of connection to public sewer- Chad - 3rd floor
06/25/2010 ROBERT SHERRY WATER REVIEW Approved
06/25/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/28/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; sheet P1 is illegible. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
06/29/2010 RONALD BROWN ZONING HC REVIEW Approved
06/29/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2010 DELMA ROBEY OUT TO CUSTOMER Completed
07/08/2010 SUE REEVES REJECT SHELF Completed