Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/16/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/16/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Specify the type of backflow device to be used for each piece of equipment. Each piece of equipment requiring backflow protection shall be independently protected. Reference: Sections 602.2 and 603.0, UPC 2006, as amended by the City of Tucson. 2. Provide a trap and vent for the indirect waste for appliance #4. Reference: Section 803.0, UPC 2006. 3. Where is appliance #9 (tea brewer) to be connected? |
07/20/2010 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/20/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |