Permit Number: T10CM01467
Parcel: 13214013A

Address:
727 E EVANS BL

Review Status: Completed

Review Details: SITE

Permit Number - T10CM01467
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Fire Department approved lock box required at gate; please refer to COT amendments to the 2006 IFC, Section 503.6.1 and 503.6.2 for details.

Provide the types and quantities of inside and outside hazardous material strorage. Sprinklers and/or fire walls may be required.
06/01/2010 RBROWN1 ADA REVIEW Passed Not a COT owned or operated property
06/02/2010 LOREN MAKUS ENGINEERING REVIEW Denied The proposed retention/detention basins don't meet the design guidelines in the detention/retention manual. The design guidelines limit the use of retaining walls to 30 percent of the basin perimeter.

The basin must be provided with access to the interior of the basin for maintenance. And a maintenance plan is required for the basin and for the pump.

Since the difference between the un-detained developed discharged and the pre-developed discharge is less than 1 cfs at the 100-year event, enhanced water harvesting would suffice for the detention requirements. Since there is a substantial storm drain system within 44th Street, the effect on the regional watershed will be minimal.

The Land Use Code 3.7.4.3.A requires all retention and detention basins not integrated with parking areas to be landscaped and designed in conformance with the design guidelines in the detention/retention manual.
06/09/2010 RONALD BROWN ZONING HC REVIEW Approved
06/09/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Airgas West Inc.
T10CM01467
Site Plan (1st Review)

TRANSMITTAL DATE: June 9, 2010

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for a greater than 25% expansion of site area.

2. This site is comprised of five (5) separate parcels and requires a lot combination. Prior to approval of this site plan provide a copy of the approved Pima County Combination Request Form, and a copy of the recorded Covenant Regarding Development and Use of Real Property along with the recordation information, docket and page.

3. Remove all existing lot lines from within this project.

4. There is a storage container shown along the northeast end of the building. Provide documentation that this container was permitted. If not permitted show as to be permitted on this site plan and include the square footage in all building calculations.

5. D.S. 2-02.2.1.A.6 Provide the height for all structures on site.

6. D.S. 2-02.2.1.A.8 Provide a typical parking space details for both handicapped and standard spaces, together with access thereto.

7. D.S. 2-02.2.1.A.8 The three (3) proposed vehicle parking spaces, located south of the existing building require some type of barrier to prevent vehicles from access the landscape area to the south and the area to the north.

8. D.S. 2-02.2.1.A.9 The proposed Class 2 bicycle parking does not meet the requirement of D.S. 2-09.5.1.B, a minimum of thirty-six (36) inches will be provided between a bicycle parking space and a perpendicular wall.

9. D.S. 2-02.2.1.A.9 The proposed Class 2 bicycle parking does not meet the requirement of D.S. 2-09.5.1.B, a minimum of thirty (30) inches will be provided between a bicycle parking space and a parallel wall or obstruction as measured from the side of the bicycle rack, not the center, to the wall.

10. D.S. 2-02.2.1.A.9 Demonstrate on the plan how the requirements of D.S 2-09.5.1.A are met. Show the required seventy-two (72) inch length per bicycle parking space.

11. D.S. 2-02.2.1.A.9 Demonstrate on the plan how the requirements of D.S 2-09.5.2 are met. A five (5) foot wide access aisle measured from the front or rear of the seventy-two inch long parking space will be provided.

12. D.S. 2-02.2.1.A.9 For your information per LUC Section 3.3.7.8.A. Any use providing less than fifty (50) motor vehicle parking spaces may substitute Class 2 spaces for Class 1 spaces. Also a single inverted "U" bicycle rack can hold two (2) bicycles.

13. D.S. 2-02.2.1.A.11 Provide a width dimension for the northwest entrance parking area access lane (PAAL) off of Evans Blvd.

14. D.S. 2-02.2.1.A.12 Per D.S. 2-08.4.1 a sidewalk is required adjacent and parallel to any PAAL on the side where buildings are located and per D.S. 3-05. a five (5) pedestrian refuge area must be maintained between any enclosed structure and a PAAL. That said provide the required sidewalk and refuge area along the northwest side of the building.

15. D.S. 2-02.2.1.A.12 Indicate on the site plan if the existing sliding gates, shown at the northeast end of the parking area, are open or closed during regular business hours. It these gates are to be closed during regular business ours show how the requirements of D.S. 3-05.2.2.D are met. A back-up spur will be provided at the end of a row of parking if no ingress or egress is provided at that end. The spur will be a minimum of three (3) feet in depth, will have a three (3) foot radii, and will have a wheel barrier to prevent encroachment onto any unsurfaced areas. A minimum distance of three (3) feet will be provided between the back of spur and any wall, screen, or other obstruction over six (6) inches in height.

16. D.S. 2-02.2.1.A.13 Zoning acknowledges the existing sign shown on the site plan, provide the type, size, and height of existing standing sign

17. D.S. 2-02.2.1.A.14 The loading space shown under keynote 5 does not meet the requirements of LUC Section 3.4.5.2; one (1) 12 x 55 foot loading space is required.

18. D.S. 2-02.2.1.A.19 Provide a fully dimensioned right of ways for all streets boarding this project.

19. D.S. 2-02.2.1.A.20 If applicable all easements of record must be graphically shown on the plan together with recording docket and page reference.

20. D.S. 2-02.2.1.A.25 If applicable show all existing and proposed site lighting layout and type.

21. D.S. 2-02.2.1.A.25 Provide the zoning for the parcels across Evans and Benson Hwy.

22. D.S. 2-02.2.2.A.2 The is a storage container shown along the northeast end of the building is to be include in the building square footage.

23. D.S. 2-02.2.2.A.3 Per Development Designator "34" and LUC Section 3.2.3.2.B Lot Coverage is not applicable, remove General Note 3 from sheet 1 and provide a Floor Area Ratio (FAR) calculation per LUC Section 3.2.11, the allowed FAR is 2.0.

24. D.S. 2-02.2.2.A.4 Per LUC Section 3.3.4 WHOLESALING USE GROUP, Business Supply and Equipment the required parking is based on Storage Area, this includes outside storage area, i.e. Gas Cylinder Storage Area, etc. Clearly indicate on the plan all area of storage and revise the parking calculation as needed.

25. D.S. 2-02.2.2.A.4 Once comment 24 has been addressed the require number of bicycle parking can be verified.

26. D.S. 2-02.2.2.A.4 Per LUC 3.3.3.5 Bicycle Parking Requirements. The number of required bicycle parking spaces is calculated as a percentage of the total number of motor vehicle parking spaces provided. If the calculated number of required bicycle parking spaces is less than two (2), the minimum number of required spaces is two (2).

27. Depending on how the above comments are addressed addition comments may be forth coming.
If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t10cm01467

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan.
06/22/2010 ANDREW CONNOR NPPO REVIEW Approved Exception
06/22/2010 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. This site is reviewed under full code compliance all landscape requirements apply.

2. A 6' continuous screen along street frontages for outdoor storage must be provided per LUC Table 3.7.2-I.

3. A 6' wall to screen loading area(s) from adjacent street frontage must be provided per LUC Table 3.7.2-I

4. All landscape areas will be depressed to accept water flow from roofs, PAAL, and parking areas. Show by detail or spot elevations how landscape areas will accommodate water harvesting.

5. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

6. Additional comments may apply.
06/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the location, invert, and rim elevation of all manholes. Reference: City of Tucson Development Standard No. 2-01.1.0 2 3.8 D and Section 103.2.3, UPC 2006

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2010 CPIERCE1 OUT TO CUSTOMER Completed
06/25/2010 SUE REEVES REJECT SHELF Completed