Permit Number - T10CM01458
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need engineer of record to verify that he has reviewed and approved the steel building drawings and specs by signing and sealing approval on front cover of spec package.
2. Need Special Inspectors Certifications submitted for review and approval
3. The 1 hour rated East wall 2' from the property line may not be under a separate contract at a later date. It must be included in this permit.
a. Please provide a full height wall section and a UL Rated assy. number.
END OF REVIEW