Permit Number: T10CM01452
Parcel: 117170010

Address:
114 S 5TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01452
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 DAVE MANN FIRE REVIEW Approved
06/01/2010 RONALD BROWN ADA REVIEW Passed Not a COT owned or operated property
06/11/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved
06/11/2010 RMYERS1 WATER REVIEW Approved
06/16/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G1.0; BUILDING CODES: THIS TENANT IMPROVEMENT IS FOR THE R-2 PORTION ONLY. PROVIDE SQUARE FOOTAGE AND OCCUPANT LOAD FOR THIS PROJECT ON SHEET G1.0.
2. SHEET A1.0; BASEMENT FLOOR PLAN: REVISE OR REMOVE NOTE 11 AT THE STAIR.
3. SHEET A1.0 (MEZZANINE PLAN); SHEET A3.0 (DETAIL 5): THE MEZZANINE PLAN INDICATES THE NEW WATER HEATER IS SUPPORTED AT THE MEZZANINE FLOOR, AND DETAIL 5 INDICATES IT IS SUPPORTED BELOW THE FLOOR (AS DOES DETAIL 1/P1.0). IS THERE ADEQUATE ROOM BELOW THE MEZZANINE FLOOR TO SUPPORT THE WATER HEATER? CLARIFY.
4. STRUCTURAL CALCULATIONS (PAGE 2): THE CALCULATIONS INDICATE THE NEW WATER HEATER IS SUPPORTED BY THE EXISTING MEZZANINE FLOOR FRAMING. IS IT HANGING BELOW THE FLOOR PER DETAILS 5/A3.0 AND 1/P1.0, OR IS IT ON TOP OF THE FLOOR? CLARIFY.
5. GENERAL: IT WILL BE NECESSARY TO RECEIVE A LETTER OF COMPLETION FOR THIS PROJECT. WHEN CONSTRUCTION ON THIS PROJECT HAS BEEN COMPLETED AND APPROVED, AND THE LETTER OF COMPLETION IS ISSUED, THE ENTIRE JULIAN DREW STUDIO (R-2 AND B OCCUPANCIES COMBINED) SHOULD BE SUBMITTED FOR A CERTIFICATE OF OCCUPANCY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/16/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
06/17/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the fan coil is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
2. Verify that the condensate drain terminates in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
06/21/2010 GERRY KOZIOL WWM REVIEW Denied need 5th floor credit evaluation
need to show location/method of connection to public sewer
need 3rd floor PCRWRD review of easement/jt use agreements, etc- Chad Amateau- 740-6547
06/25/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2010 CPIERCE1 OUT TO CUSTOMER Completed
06/25/2010 CPIERCE1 REJECT SHELF Completed