Permit Number: T10CM01446
Parcel: 126210300

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM01446
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 6-25-10
Activity: T10CM01446
Address: 3236 E Via Palos Verdes
Applicant: PGR Construction

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans including revisions, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:
3. Show barrier between house and pool to meet enclosure criteria for swimming pools, AG105.2 as amended.

PLUMBING PLAN:
4. Provide water piping design for proposed new faucets, P2903.7.
5. Provide gas piping design for proposed gas connection to ramada, G2413.1.

OUTDOOR LIGHTING CODE
6. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
06/28/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/01/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
07/01/2010 CINDY AGUILAR REJECT SHELF Completed