Permit Number: T10CM01445
Parcel: 107040130

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01445
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
05/26/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
05/26/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the connection of the mounting shelf for the water heater to the building along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
05/26/2010 ROBERT SHERRY WATER REVIEW Denied Verify the size and location of the water meter and backflow preventer serving the two building.
05/27/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/27/2010 GBONILL1 WWM REVIEW Needs Review
05/27/2010 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/27/2010 PAUL MACHADO ENGINEERING REVIEW Approved
05/27/2010 MARTIN BROWN FIRE REVIEW Approved
05/27/2010 RONALD BROWN ZONING HC REVIEW Approved
05/27/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/27/2010 RONALD BROWN ADA REVIEW Passed