Permit Number: T10CM01439
Parcel: 131113640

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING-WALKTHRU

Permit Number - T10CM01439
Review Name: RESIDENTIAL BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2010 MICHAEL ST. PAUL ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T10CM01439
2312 South Jefferson Avenue
Addition to SFR


TRANSMITTAL: June 15, 2010


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO).



This Site requires a DDO for the setbacks to the front and the north property lines. This site is in the R-1 Zone (LUC Section 2.3.4.2.A.1). The Development Designator is "G" (LUC Section 3.2.3.1.B) and the Perimeter Yard Indicator AA (LUC Section 3.2.6.4).

The minimum setback from the front of the structure to the front (east) property line is the greater of twenty (20) feet or one and one-half (1 ½) times the height of the wall facing the property line (LUC Section 3.2.6.5). The required setback is twenty (20) feet to the front property line. The proposed setback is fourteen (14) feet.
06/15/2010 MICHAEL ST. PAUL NPPO REVIEW Passed
08/02/2010 JASON GREEN ENGINEERING REVIEW Approved
08/02/2010 DROBEY1 BUILDING-RESIDENTIAL REVIEW Needs Review