Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM01432
Parcel: 116300120

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01432
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1; SHEET S1.1; PLAN NOTES: PROVIDE A MINIMUM 3/32" HIGH LETTERING PER CITY OF TUCSON REQUIREMENTS.
2. PREVIOUS COMMENT 3; SHEET S3.1; PLAN NOTES AND WALL SCHEDULE: PROVIDE A MINIMUM 3/32" HIGH LETTERING PER CITY OF TUCSON REQUIREMENTS.
3. PREVIOUS COMMENT 4; SHEET S3.1 (FRAMING PLAN); STRUCTURAL CALCULATIONS (B17 ON SHEET 8): THE CALCULATIONS INDICATE BEAM B17 TO BE 2-2X8, WHILE THE FRAMING PLAN INDICATES 2-2X6. CLARIFY.
4. PREVIOUS COMMENT 5; SHEETS S3.1 AND S3.2 (PLAN NOTES); STRUCTURAL CALCULATIONS (SHEET 9): THE TABLE IN THE CALCULATIONS INDICATES ALL WALL STUDS TO BE 2X6 AT 16" 0.C., WHILE THE PLAN NOTES INDICATE 2X4 AT 16" O.C. OR 24" O.C. CLARIFY.
5. PREVIOUS COMMENT 6; SHEET S4.1; DETAILS 2 AND 3: REVISE THE LEVEL OF WALL SHADING SO INFORMATION IS NOT HIDDEN.
6. PREVIOUS COMMENT 7; GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.