Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01432
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 1; SHEET S1.1; PLAN NOTES: PROVIDE A MINIMUM 3/32" HIGH LETTERING PER CITY OF TUCSON REQUIREMENTS. 2. PREVIOUS COMMENT 3; SHEET S3.1; PLAN NOTES AND WALL SCHEDULE: PROVIDE A MINIMUM 3/32" HIGH LETTERING PER CITY OF TUCSON REQUIREMENTS. 3. PREVIOUS COMMENT 4; SHEET S3.1 (FRAMING PLAN); STRUCTURAL CALCULATIONS (B17 ON SHEET 8): THE CALCULATIONS INDICATE BEAM B17 TO BE 2-2X8, WHILE THE FRAMING PLAN INDICATES 2-2X6. CLARIFY. 4. PREVIOUS COMMENT 5; SHEETS S3.1 AND S3.2 (PLAN NOTES); STRUCTURAL CALCULATIONS (SHEET 9): THE TABLE IN THE CALCULATIONS INDICATES ALL WALL STUDS TO BE 2X6 AT 16" 0.C., WHILE THE PLAN NOTES INDICATE 2X4 AT 16" O.C. OR 24" O.C. CLARIFY. 5. PREVIOUS COMMENT 6; SHEET S4.1; DETAILS 2 AND 3: REVISE THE LEVEL OF WALL SHADING SO INFORMATION IS NOT HIDDEN. 6. PREVIOUS COMMENT 7; GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |