Permit Number: T10CM01432
Parcel: 116300120

Review Status: Completed

Review Details: OTHER

Permit Number - T10CM01432
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.1; PLAN NOTES: PROVIDE A MINIMUM 3/32" HIGH LETTERING PER CITY OF TUCSON REQUIREMENTS.
2. SHEET S1.1; FOUNDATION PLAN: REVISE THE LEVEL OF WALL SHADING SO INFORMATION ON THE PLAN IS NOT HIDDEN.
3. SHEET S3.1; PLAN NOTES AND WALL SCHEDULE: PROVIDE A MINIMUM 3/32" HIGH LETTERING PER CITY OF TUCSON REQUIREMENTS.
4. SHEET S3.1 (FRAMING PLAN); STRUCTURAL CALCULATIONS (B17 ON SHEET 8): THE CALCULATIONS INDICATE BEAM B17 TO BE 2-2X8, WHILE THE FRAMING PLAN INDICATES 2-2X6. CLARIFY.
5. SHEETS S3.1 AND S3.2 (PLAN NOTES); STRUCTURAL CALCULATIONS (SHEET 9): THE TABLE IN THE CALCULATIONS INDICATES ALL WALL STUDS TO BE 2X6 AT 16" O.C., WHILE THE PLAN NOTES INDICATE 2X4 AT 16" O.C. OR 24" O.C. CLARIFY.
6. SHEET S4.1; DETAILS 2 AND 3: REVISE THE LEVEL OF WALL SHADING SO INFORMATION IS NOT HIDDEN.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
07/26/2010 SUE REEVES REJECT SHELF Completed