Permit Number: T10CM01425
Parcel: 129041820

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM01425
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: T10CM01425 , 2008 E Broadway
Photo Voltaic System
The Electrical plans have been denied for the following:

1. The electrical drawings to be sealed by an Electrical Engineer.
2.Provide the locations of the AC disconnets, inverter, on a floor plan or Sheet A1.0.
3. Describe the manner in which the # 6 conductors will tie into the gutter. A tap rule may be involved limiting the distance from gutter to ACdisconnect #2.What will the distance be ?
4.Provide under Special Notes, Installation to comply with NEC 2005.
5. The "CONT. #10 EQG" labeled on Sheet E1.0 is incorrect, this is a Grounding Electrode Conductor and must be sized for AC and DC grounding systems per 2005 NEC 690-47.


Ray T Majuta, Elect Pln Ck,
PDSD, City of Tuc,
6/22/10,