06/14/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/21/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT: T10CM01425 , 2008 E Broadway Photo Voltaic System The Electrical plans have been denied for the following: 1. The electrical drawings to be sealed by an Electrical Engineer. 2.Provide the locations of the AC disconnets, inverter, on a floor plan or Sheet A1.0. 3. Describe the manner in which the # 6 conductors will tie into the gutter. A tap rule may be involved limiting the distance from gutter to ACdisconnect #2.What will the distance be ? 4.Provide under Special Notes, Installation to comply with NEC 2005. 5. The "CONT. #10 EQG" labeled on Sheet E1.0 is incorrect, this is a Grounding Electrode Conductor and must be sized for AC and DC grounding systems per 2005 NEC 690-47. Ray T Majuta, Elect Pln Ck, PDSD, City of Tuc, 6/22/10, Ray.Majuta@tucsonaz.gov |