Permit Number: T10CM01424
Parcel: 129041830

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM01424
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2010 DAVE MANN FIRE REVIEW Approved
06/16/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.0 (ROOF FRAMING LAYOUT); SHEET D1.0 (DETAIL 2): AT THE NORTHWEST ARRAY, THERE ARE TWO STAND OFF'S (AT SINGLE PANELS) THAT ARE NOT LOCATED DIRECTLY OVER AN EXISTING STEEL TRUSS. DETAIL 2/D1.0 AND THE CALCULATIONS INDICATE ALL MOUNTS ARE TO BE LOCATED ON THE JOISTS. CLARIFY.
2. GENERAL: PROVIDE A WRITTEN RESPONSE TO THE REVIEW COMMENT.
06/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2010 CPIERCE1 OUT TO CUSTOMER Completed
06/24/2010 SUE REEVES REJECT SHELF Completed