Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01412
Parcel: 13315058A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01412
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The submitted dryer listing calls for a 4" diameter rigid metal exhaust duct or, if that is not possible, a 4" diameter flexible metal foil duct may be used provided the 4" diameter size can be maintained for the entire duct run. The listing does not allow for the use of any other duct sizes. Reference: Sections 304.1 and 504.6, IMC 2006.
06/02/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006
06/04/2010 GBONILL1 WWM REVIEW Needs Review