Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM01412
Parcel: 13315058A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01412
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2010 STEVE SHIELDS ZONING REVIEW Approved
05/24/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide listing information for the clothes dryer to show that the proposed 3.5"x 6" dryer exhaust duct is sized correctly. Reference: Sections 304.1 and 504.6, IMC 2006.
05/24/2010 ERIC NEWCOMB ADA REVIEW Passed
05/24/2010 ROBERT SHERRY WATER REVIEW Approved
05/24/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/24/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
05/24/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide fixture descriptions for all plumbing fixtures (e.g. shampoo sink) All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.
2. Provide the minimum plumbing facilities (e.g. drinking fountain) required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy.
3. Correct the water pressure loss calculations. Unless the water service piping is galvanized steel, the maximum water velocity is 8fps. The fixtures noted in the demand calculation do not appear in the suite, and the water fixture units do not appear to be from the 2006 UPC,
4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
05/24/2010 DAVE MANN FIRE REVIEW Approved
05/24/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
05/24/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/25/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/02/2010 CAGUILA1 WWM REVIEW Needs Review