Permit Number: T10CM01383
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01383
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Drawings can not be approved until the revised sheets are bound into the full set of construction drawings.
06/29/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/29/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Clarify how the bracket depicted in detail B/MP511 can be constructed from 1-1/2" x 1-1/2" x ΒΌ" angle. Provide additional construction information for detail B/MP511: what are the dimensions of the bracket? Reference: Sections 106.3.1 and 305.2, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2010 CPIERCE1 OUT TO CUSTOMER Completed
08/04/2010 CPIERCE1 REJECT SHELF Completed