Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Drawings can not be approved until the revised sheets are bound into the full set of construction drawings.
06/29/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/29/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Clarify how the bracket depicted in detail B/MP511 can be constructed from 1-1/2" x 1-1/2" x ΒΌ" angle. Provide additional construction information for detail B/MP511: what are the dimensions of the bracket? Reference: Sections 106.3.1 and 305.2, IMC 2006.