Permit Number: T10CM01383
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01383
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2010 DAVE MANN FIRE REVIEW Approved
06/03/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide completed Special Inspection Certificates for field welding, concrete and epoxy anchors.
2. Please clarify detail 1/S310. Calculations call out a fully grouted 8" cmu wall wheras the detail shows an top 8" bond beam only.
3. Minimum font size requirement is 3/32" both upper and lower case. Sheet M1614 needs to be reworked to meet this requirement.
END OF REVIEW
06/10/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the routing of the boiler condensate piping complies with the intent of Section 811.4, UPC 2006.
06/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide sizes for the hanger rods shown in detail E/MP511. Reference: Section 305.2, IMC 2006.
2. Provide additional construction information for detail B/MP511: what are the dimensions of the bracket, the u-bolts, and the wall anchors? For what size pipe does this detail apply? Reference: Sections 106.3.1 and 305.2, IMC 2006.
3. Revise detail A/MP511 to utilize a support that is suitable for the intended use. The Miro 8-DSA duct and cable tray support is limited to a maximum duct diameter of 26" according to the manufacturer. Reference: Sections 106.3.1 and 305.2, IMC 2006.
06/17/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved