Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01334
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/25/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/25/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
05/25/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the pipe sizes shown in the waste plan and the waste isometric to comply with the minimum sizes shown in Table 7-5, UPC 2006. 2. Clarify the intent of the 1" drain line shown running from the water heater location to the mop sink. If it is intended only to act as a drain for the pan under the water heater, it should terminate over the mop sink with an air break. Reference: sections 103.2.3, 508.4, and 812.0, UPC 2006. 3. Provide cleanouts sized per Table 7-6, UPC 2006. |
05/25/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
05/25/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/25/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Clarify the location of the exhaust fans for the restrooms. 2. Indicate the minimum damper rating for the new fire dampers. Reference: section 607.3.1, IMC 2006. |
06/16/2010 | CPIERCE1 | WWM | REVIEW | Needs Review |