Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01334
Parcel: 11301146Y

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01334
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/25/2010 DAVE MANN FIRE REVIEW Approved
05/25/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the pipe sizes shown in the waste plan and the waste isometric to comply with the minimum sizes shown in Table 7-5, UPC 2006.
2. Clarify the intent of the 1" drain line shown running from the water heater location to the mop sink. If it is intended only to act as a drain for the pan under the water heater, it should terminate over the mop sink with an air break. Reference: sections 103.2.3, 508.4, and 812.0, UPC 2006.
3. Provide cleanouts sized per Table 7-6, UPC 2006.
05/25/2010 RONALD BROWN ZONING HC REVIEW Approved
05/25/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/25/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Clarify the location of the exhaust fans for the restrooms.
2. Indicate the minimum damper rating for the new fire dampers. Reference: section 607.3.1, IMC 2006.
06/16/2010 CPIERCE1 WWM REVIEW Needs Review